ACP Portable Electrical Current Transformer Test,CT/PT Analyzer

ACP current transformer test kit is the most complete and easy-to-use testing system for protection and metering CTs according to IEEE and IEC standards.

ACP portable current transformer test kit designed for analyzing current transformers and voltage transformers of protection or measurement use, which is suitable for laboratory and on-site test.

Description

Application:
ACP portable Current transformer analyzer is mainly used for field or lab testing, it can finish the measurements (M) and protection (P) class CT, PT and TYP class CT. Adopt 7 inch touch TFT LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data. The CT PT Analyzer is the most complete and easy-to-use testing system for protection and metering CTs according to IEEE and IEC standards.

Tests for current transformer:

1.Excitation curve and parameters test
2.Turns ratio test
3.Ratio and phase error test
4.Polarity mark check
5.Coil resistance measurement
6.Secondary loop burden measurement
7.Error line curve test for protection CT
8.Transient CT parameters test
9.CT nameplate guess
10.Saturation hysteresis loop curve measurement

current transformer test
current transformer test

ACP Current Transformer Test Kit's Technical Parameters

No.

Item Name

ACP Current Transformer and Voltage Transformer CT PT Analyzer

1

Test standards

IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13

2

Power supply

AC220V±10%,50Hz/60Hz±10%

3

Power output

0.1~125V (AC)

4

Current output

0.001~5A(RMS)

5

Power output

300VA

6

Max. knee voltage measurement

45kv

7

Current measurement range

0~10A (automatically change range in 0.1/0.4/2/10A)

8

Current measurement error

<±0.1%+0.01%FS

9

Voltage measurement range

0~200 V (automatically change range in 1V/10V/70V/200V)

10

Voltage measurement error

< ±0.1%+0.01%FS

11

Turns ratio measurement range

1~30000;

1~2000 error<0.05%;    

2000~5000 error>0.1%;   

5000~35000 error<0.2%

12

Phase measurement

error: ±2min,resolution:0.01min

13

Coil resistance measurement

Range: 0~8kΩ(automatically change range in 2ohm /20ohm /80ohm/800ohm/8kohm)

Error< 0.2%RDG+0.02%FS     

                   Maximum resolution: 0.1mΩ

14

Temperature measurement

-50~100 Celsius degree, error<3 Celsius degree

15

CT Secondary burden

Range 0-160ohm (automatically change range in 2ohm/ 20ohm/80ohm/160ohm)

                     Error<0.2%RDG+0.02%FS    Maximum resolution 0.001ohm

16

PT Secondary burden

Range 0-80kohm (automatically change range in 800ohm / 8kohm /80kohm)

                          Error<0.2%RDG+0.02%FS      

                             Maximum resolution: 0.1ohm

17

PT ratio measurement

Range: 1~30000

 1~5000 error<0.2%     

5000~30000 error<0.5%

18

Saved data groups

>1000groups

19

Work condition

Temperature: -10℃-50℃, moist: ≤90%

20

Size

485mm*356mm*183mm

21

Weight

<15Kg

Ask for a quote