Description
FPR EHC Hydraulic Oil Filtration Plant
specially designed for regeneration of the fire-resistant hydraulic oil and EH phosphate ester fire-resistant oil from the speed control system of 300,000KW’s generator sets and above.
Application
FPR series EHC Hydraulic Oil Filtration Plant can be used in many industries. The typical practice includes processing EH oil in power turbine control system(Electro Hydraulic Controls).
This oil filtration system is designed according to the properties and working condition of phosphate ester base fire-resistant hydraulic fluids, and therefore can greatly extend the oil’s service life
- Machine body made of high quality SUS material
- Removing moisture, gases and solid impurities all in one process
- High efficiency moisture separation with coalesce & vacuum dehydration
- Keep water content in oil down to 50 ppm
- Filtration stage and fineness rating customizable
- Quick demulsification technology
- Low watt density heating element
- Interlocked safe protection with alarm
- Automatic/Manual operation switch
- Robust design & easy maintenance
Features
1.High Efficiency Acid Removal and Dehydration.
2.Equips with a new and efficient regeneration system and dehydration chamber, which can quickly reduce the acid value and moisture of the fire-resistant oil, increase its resistivity, and restore the physical and chemical properties of the oil.
3.Cleanliness up to NAS grade 5.
4.The tank and pipelines where fire-resistant oil going through are all made of 304 stainless steel, Anti-acid and corrosion resistance type sealing, filter elements.
5.Compact structure and easy operation.
FPR EHC Hydraulic Oil Filtration's Technical Parameters
Item | Parameter | Type | FPR-10 | FPR-20 | FPR-30 | FPR-50 | |
Technical Parameter | Flow Rate | L/MIN | 10 | 20 | 30 | 50 | |
Working Vacuity | Mpa | -0.09 | |||||
Working pressure | Mpa | ≤0.5 | |||||
Temperature Range | °C | 45-65 | |||||
Power Supply | 50Hz 380V 3-Phase 4-Wire (or as requested) | ||||||
Total Power | KW | 10 | 12 | 13.5 | 33 | ||
Inlet/Outlet Diameter | mm | 32 | 48 | ||||
Size | Length | mm | 1200 | 1200 | 1200 | 1600 | |
Width | mm | 940 | 960 | 1000 | 1200 | ||
Height | mm | 1550 | 1550 | 1600 | 2000 | ||
Weight | Kg | 380 | 400 | 420 | 500 |
After Treatment
Oil Treatment Index | Water Content | ppm | ≤50 |
Filtering Accuracy | µm | ≤1 | |
Cleanliness | NAS | ≤NAS 1638 Grade 5 | |
Acid Value | Mg KOH/g | ≤0.03 | |
Resistivity | cm | ≥6×109 (DL/T 421) |